Certification: | CE/ROHS/CESI/CTQC | model: | voltage control transformer |
Coil structure: | ring | brand: | monastery |
Product Category: | voltage control transformer | OEM/Design Manufacturer: | usable |
Packaging Details: | Voltage Control Transformer 1) 1 plastic bag/set, 1 wooden box/set 2) Special packing as required by customers. | Advantage: | Best price and best quality in China |
standard: | IEC60076, GB1094-1996; JB/T10088-2004; GB/T6451-2008; EQV | Transformer type: | isolation transformer |
usage: | strength | Primary voltage: | Customized/AC 110V, 115V, 120V, 127V, 220V, 230V, 240V, etc. |
Supply capacity: | 35,000 pieces of voltage control transformers per month | stage: | one or three |
Secondary voltage: | Customized/AC 12V, 24V, 36V, 48V, 120V, 240V, etc. | Origin: | Zhejiang, China |
port: | Ningbo, Shanghai, Wenzhou | payment terms: | L/C, T/T, Western Union, MoneyGram, PayPal, Credit Card |
Number of coils: | Autotransformer | Rated Capacity: | 10VA to 25000VA |
frequency: | 50Hz or 60Hz |
Voltage controlled transformer ip67 instantaneous waterproof switch transformer copper for toys
380V/220V 200V 180V 48V 24V 12V 6.3V Machine Tool Isolation Transformer Manufacturervoltage control transformer
Specification:
BK series machine tool control transformers are suitable for 50~60Hz, voltage up to 500V circuits, and are usually used as power supplies for machine tool electrical appliances, local lighting and indicator lights.
1. Input voltage: rated voltage ±10%
2. Output voltage: rated voltage +5% (no load)
3. Efficiency: ≥95%
4. Waveform distortion: no additional waveform distortion
5. Function: input voltage, output voltage, current indication.
6. Protection: overcurrent protection
7. It can be operated unattended for a long time
8. Insulation resistance: ≥50MΩ
9. Electric strength: power frequency sinusoidal voltage 2000V 1min without breakdown or flashover phenomenon
10. Overload capacity: 1min at 2 times rated current
voltage control transformer
working environment:
1. Ambient temperature: -15℃~+40℃
2. Altitude: <1000m
3. Relative humidity: <90%
4. There are no gases, vapors, chemical deposits, dust or dirt that seriously affect the insulation of the transformer in the environment, and explosive or corrosive media are not allowed.
5. If the special working conditions do not meet the above requirements, the user should negotiate with us.voltage control transformer
Different kinds of transformers we offer:
Trade terms:
1. Payment method:1) 30% prepayment, the balance 70% paid before shipment. 2) Letter of credit
2. Port of loading:Ningbo, Wenzhou or Shanghai port
3. Discount:Available according to order quantity
4. Delivery time:3-10 days according to the order quantity.
voltage control transformer
Feedback: copper transformer toy
We really appreciate your positive feedback. We take our customers very seriously. If you have any questions, please feel free to contact us by email, we are always here to help.
voltage control transformer