KRIWAN Motor Protector SE-E1 Compressor Protection Module INT69 INT69 CN SE-B1 SE-B2

Product details
Package:wooden boxbrand:Krivan, Krivan
brand:KrivanMOQ:1
Warranty:one yearPackage preview:
model:SE-E1Types of:Krivan
describe:INT69 FSYplace of origin; place of origin:Germany
Product Description
The world's compressor control and protection industry giant Germany KRIWAN began to produce INT series compressor control protectors and PTC thermistors in 1966. The company has a long history and its products are well-known in the international market. It is recognized as the best choice for controlling compressors. In Europe, Keruiwen's products are used in almost all compressors, with a market share as high as 90%.
This product is also selected as the designated product in the refrigeration industry by major compressor manufacturers in the world
Industries, including YORK York, REFCOMP, Italy Dorin Turin, frascold, BITZER, German Boke Blog Company, Taiwan Hanbell Hanzhong Company, etc.
introduce:
Used to monitor compressor motor winding temperature, exhaust temperature, power phase sequence and phase failure
Cooling System.
It must be used with a PTC thermistor to prevent excessive motor temperature and exhaust temperature.
It can monitor the value of 1-9 strings of PTC thermistors in the motor. If one or more PTC resistors are in a high-impedance state, the motor
The protector relay releases and self-locks.
feature:
1. Enable the phase sequence monitoring function within 5 seconds after power on. Once the phase sequence is wrong, the relay switch
Disconnect and self-locking.
2. After the motor starts for 1 second, the phase loss monitoring function works. Once a phase loss fault is detected, the motor will rotate
Leave; after 10S, monitor again to reset automatically; if 3 times of phase-loss faults are detected within 12 minutes, that is, 10 phases
Loss is detected within 24 hours. In the event of a malfunction, the protector locks automatically.
3. If PTC failure is detected multiple times, it will lock itself. Phase sequence monitoring and phase loss monitoring are
It is valid after power on; once any fault is detected, the relay switch is turned on and self-locked.
4. The power supply can be automatically unlocked after 5 seconds of power failure.
5. This protector is not suitable for inverter side.